Home»Products» Electrical Devices in Power Industry » Three-phase Oil-immersed Distribution Transformer » Three-phase Hermetically Sealed Oil-immersed Distribution Transformer

Three-phase Hermetically Sealed Oil-immersed Distribution Transformer

The three-phase hermetically sealed oil-immersed distribution transformer could be classified into three series which are S9, S11 and S13. They have different properties and application ranges as demonstrated below.

Features
1. The S9 series has a wide power range of 6.3-2500kVA, and it fits for 10KV power transmission and distribution system with frequency of 50Hz or 60Hz.

2. The S11 series is applicable for 6KV and 10KV transmission and distribution systems. Compared with S9, this product possesses lowered no-load loss and better energy saving result. Moreover, the noise level conforms to environmental protection policy. Thus, the S11 series hermetically sealed oil-immersed distribution transformer could be called an energy saving and environmental friendly product.

3. The S13 series is based on the three dimensional triangular wound core, and remarkable energy saving performance is obtained. When compared with S11, the S13 series further improves its behavior. For example, the no-load loss is reduced by 25%, the no-load current is cut down by 60%-80%, and the noise level is lowered by as much as 30%-40%. Due to the low loss, low noise, attractive appearance, good performance, maintenance free and long life span, this device is truly a high technology, high performance, energy saving and environmental friendly product.

Applications
Depending on the different properties and technical data, the three series of hermetically sealed oil-immersed distribution transformer could be used in various places.
The S9 series is commonly accepted for lighting and powering purposes in residential areas, business streets, rural places, industrial and mining enterprises, etc.
The S11 series is suitable for factories, mining plants, agricultural and petrochemical engineering industries to power lighting lamps and production equipment.
The S13 series is usually used in 10KV power distribution systems.

Technical Parameters for 10KV S11 Series
Model Rated
power
(kVA)
Voltage combination Vector
group
Loss (W) No-load
current
(%)
Impe-
dance
voltage
(%)
Dimensions
(L×W×H, mm)
Weigh(kg)
HV
rating
(kV)
Tapping
range
(%)
LV
rating
(kV)
No-load
loss
Full-load
loss
Oil Total
S11-6.3 6.3 6
6.3
6.6
10
10.5
11
13.2
15
20
30
33
±2×2.5%,
±3×2.5%
 or ±5%
0.4,
0.415
or
others
Yyn0
or
Dyn11
0.035 0.219 4.0 4.0 910×450×985 52 168
S11-10 10 0.045 0.306 3.3 4.0 960×450×1010 62 210
S11-15 15 0.058 0.360 2.2 4.0 970×450×1010 78 220
S11-20 20 0.080 0.521 2.2 4.0 1000×630×1020 80 240
S11-25 25 0.090 0.577 2.1 4.0 1020×630×1020 85 250
S11-30 30 0.10 0.60 1.3 4.0 1050×630×1040 90 400
S11-50 50 0.31 0.87 1.1 4.0 1020×680×1080 100 460
S11-63 63 0.15 1.04 1.0 4.0 1060×690×1090 110 500
S11-80 80 0.18 1.25 0.9 4.0 1070×700×1100 115 550
S11-100 100 0.20 1.50 0.8 4.0 1090×710×1100 120 620
S11-125 125 0.24 1.80 0.8 4.0 1130×730×1180 145 700
S11-160 160 0.28 2.20 0.7 4.0 1160×750×1180 175 830
S11-200 200 0.34 2.60 0.7 4.0 1190×750×1260 190 910
S11-250 250 0.40 3.05 0.6 4.0 1230×770×1280 200 1000
S11-315 315 0.48 3.65 0.6 4.0 1260×830×1290 220 1190
S11-400 400 0.56 4.30 0.5 4.0 1310×830×1340 260 1430
S11-500 500 0.68 5.10 0.5 4.0 1389×889×1380 280 1600
S11-630 630 0.81 6.20 0.5 4.5 1490×980×1410 330 1830
S11-800 800 0.98 7.50 0.4 4.5 1560×1000×1560 450 2300
S11-1000 1000 1.15 10.30 0.4 4.5 1700×1130×1650 550 2700
S11-1250 1250 1.36 12.00 0.3 4.5 1630×1230×1710 630 3200
S11-1600 1600 1.64 14.50 0.3 4.5 1980×1270×1790 800 3700
S11-2000 2000 1.98 17.80 0.3 4.5 1980×1310×1900 1050 4500
S11-2500 2500 2.31 20.70 0.3 5.5 2360×1580×2300 1200 5500

Note: The above data are typical values and are for reference only. Customized products are supplied upon request.

Related Names
Oil Insulated Power Transformer | Substation Power Transformer | 3 Phase Step Down Transformer

Related products
Inquiry Form